The Fire Smoke Damper is designed to provide combined fire and smoke protection in HVAC ventilation and smoke management systems. It is suitable for installation in fire-rated walls and floors with a fire resistance rating of up to 1.5 hours, subject to the applicable certified configuration.Designed for dynamic operation, the damper supports both vertical and horizontal installation with airflow in both directions.

Brand
kbe
Min Order Qty
1
Material
Galvanized steel
kbe
kbe
View Brand Profile

Technical Specifications

Product Type Combination Fire and Smoke Damper
Fire Resistance Rating 1.5 Hours
Fire Classification UL 555 (Model Dependent)
Smoke Classification UL 555S (Model Dependent)
Application HVAC and Dynamic Smoke Management
Mounting Orientation Vertical and Horizontal
Airflow Direction Both Directions
Maximum Static Pressure 4 in. W.G. (1000 Pa)
Maximum Air Velocity 4000 FPM (20.3 m/s)
Maximum Operating Temperature 350°F (177°C)
Frame Material Galvanized Steel
Frame Thickness 16 Gauge (1.6 mm)
Blade Material Galvanized Steel
Blade Thickness 16 Gauge (1.6 mm)
Blade Design Three-V Formed
Bearing Type Oil-Impregnated Sintered Bronze
Axle Material Zinc-Plated Steel
Blade Seals Silicone
Blade Seal Temperature Rating 450°F (232°C)
Jamb Seals 300 Series Stainless Steel
Closure Device Electronic Fusible Link or Approved Alternative
Closure Temperature 165°F (74°C) for RS-100 configuration
Finish Mill Galvanized
Sleeve Shape Rectangular
Actuator Type Electric Spring Return or Pneumatic
Actuator Voltage 24V, 120V or 230V
Minimum Single Section Size 8 x 8 inches (203 x 203 mm)
Maximum Single Section Size 36 x 36 inches (914 x 914 mm)
Optional Bearings Stainless Steel
Optional Construction Stainless Steel
Optional Sleeve Shapes Round, Oval and Special